Features
- ACCORDING TO IEC 60502-2
Resistance
FLAME RETARDANT ACC. TO
DIN VDE 0482 PART 265-2-1
EN 50265-2-1
EN 60332-1-2
STRANDED RED COPPER CONDUCTOR CL. 2, ACC. TO IEC 60228
SEMI-CONDUCTING COMPOUND
RUBBER TYPE G7
SEMI-CONDUCTING RUBBER COMPOUND
RED COPPER TAPE
NOT HYGROSCOPIC FILLER
RED (RAL 3000), PVC TYPE RZ
DIN VDE 0482 PART 265-2-1
EN 50265-2-1
EN 60332-1-2
NOMINAL VOLTAGE :
Uo/U 1,8/3 kV, Uo/U 3,6/6 kV,
Uo/U 6/10 kV, Uo/U 8,7/15 kV,
Uo/U 12/20 kV, Uo/U 18/30 kV,
Uo/U 26/45 kV
TEST VOLTAGE :
Uo/U 1,8/3 kV = 6 kV,
Uo/U 3,6/6 kV = 11 kV,
Uo/U 6/10 kV = 17 kV,
Uo/U 8,7/15 kV = 24 kV,
Uo/U 12/20 kV = 29 kV,
Uo/U 18/30 kV = 45 kV
MAX. OPERATING VOLTAGE :
Uo/U 1,8/3 kV = Um 3,6 kV
Uo/U 3,6/6 kV = Um 7,2 kV
Uo/U 6/10 kV = Um 12 kV
Uo/U 8,7/15 kV = Um 17,5 kV
Uo/U 12/20 kV = Um 24 kV
Uo/U 18/30 kV = Um 36 kV
Uo/U 26/45 kV = Um 52 kV
TEMPERATURE RANGE :
-15°C UP TO +90°C
MAX. SHORT CIRCUIT TEMPERATURE :
+250°C
MAX. INSTALLATION TEMPERATURE :
0°C
MIN. BENDING RADIUS :
12 x D
MAX. TENSILE STRESS :
60 N/MM2